E19 Repeated outdoor fan / board faults (critical)
What the control is telling you
Thermostat shows 19, outdoor board display shows E19. The outdoor fan motor or its drive on the control board keeps faulting.
Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)
Likely causes
- Something blocking the outdoor fan
- Fan motor not plugged in right
- Outdoor fan motor not running
- Bad control board
- Electrical noise
Test and repair steps
- Kill power at the disconnect before opening the control box or touching wiring.
- Clear debris from the fan grille and make sure the blade turns free.
- Check the fan motor wiring back to the control board.
- Check the outdoor fan motor. Replace it if it has failed.
- Replace the control board only if the motor and wiring are good.
Models that show this code
11 models in Daikin FIT DH6VS/DH7VSA
Other codes on the same units
- E13 Repeated high pressure faults (critical)
- E15 Repeated low pressure faults (critical)
- E17 Repeated compressor faults (critical)
- E18 Control board may need replacing (outdoor fan drive)
- E20 Outdoor EEV fault
- E21 Repeated low discharge superheat faults
- E22 Repeated high discharge temperature faults
- E23 Discharge temperature sensor out of range
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.