Daikin · Heat pump

E15 Repeated low pressure faults (critical)

High severity Daikin FIT DH6VS/DH7VSA

What the control is telling you

Thermostat shows 15, outdoor board display shows E15. The unit keeps tripping on low pressure. This is the critical level of the fault.

Applies to: DH6VS***1*A*, DH7VSA[24-48]10A* (FIT and Enhanced Capacity/High Efficiency FIT)

Likely causes

  • Stop valve not fully open
  • Restriction in the refrigerant lines
  • Low charge or a refrigerant leak
  • Pressure sensor bad or not plugged in right
  • Indoor blower motor not working right
  • Bad indoor or outdoor EEV, or its coil
  • Bad control board

Test and repair steps

  1. Kill power at the disconnect before opening the control box or touching wiring.
  2. Open both stop valves all the way.
  3. Look for a restriction in the line set.
  4. Check the charge. Leak test the system if it is low.
  5. Check the pressure sensor plug and the sensor.
  6. Check the indoor and outdoor EEV and their coils.
  7. Check the indoor blower motor and its wiring.
  8. Replace the control board only after the checks above.

Models that show this code

11 models in Daikin FIT DH6VS/DH7VSA

DH6VS*181DH6VS*241DH6VS*301DH6VS*361DH6VS*421DH6VS*481DH6VS*601DH7VSA2410DH7VSA3610DH7VSA4210DH7VSA4810

Other codes on the same units

  • 57 Sweating on the board cooling loop
  • E11 System start-up test not done
  • E12 Control board memory error
  • E13 Repeated high pressure faults (critical)
  • E17 Repeated compressor faults (critical)
  • E18 Control board may need replacing (outdoor fan drive)
  • E19 Repeated outdoor fan / board faults (critical)
  • E20 Outdoor EEV fault

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Daikin 3P761829-1B FIT outdoor unit DC6VS/DH6VS/DC9VSA/DH7VSA installation & service reference, Troubleshooting table p.43 (printed page). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.