Carrier · Heat pump

Status code recall Status code recall mode (25VNA8/24VNA9)

Menu / mode display Carrier Infinity 18VS 25VNA8

What the display is showing

Mode that replays the most recent, highest-priority active status code on the amber STATUS LED. Active codes are kept in memory even without power. The unit does not heat or cool while the forced defrost pins are shorted.

Applies to: Carrier Infinity 25VNA8/24VNA9

What to do

  1. Turn the unit power OFF.
  2. Short the FORCED DEFROST connector (J2 on the board) with a clip wire.
  3. Turn power ON; the amber LED flashes the stored code.
  4. Read the code (short flashes = first digit, long flashes = second digit).
  5. Power down and remove the short.

Models that show this code

7 models in Carrier Infinity 18VS 25VNA8

25VNA81325VNA82425VNA82525VNA83625VNA83725VNA84825VNA860

Other codes on the same units

  • LED1 MOC red LED1 (sizes 25-60)
  • LED3 MOC amber LED3 (sizes 25-60)
  • LED200 MOC red LED (sizes 13, 24B)
  • LED207 MOC amber LED (sizes 13, 24B)
  • COMM LED Green COMM LED on - communicating
  • Charging mode Refrigerant charging mode (25VNA8/24VNA9, communicating)
  • Curtailment Utility curtailment shown on user interface
  • ON Amber STATUS LED on solid - standby

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Carrier 25VNA8/24VNA9 service manual, Status Codes - Status Code Recall Mode, p.14. Summarized in our own words; check the original manual for your model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.