Carrier · Heat pump
Forced defrost Forced defrost (short the defrost pins)
What the display is showing
Test function that starts a defrost cycle by hand. A full defrost runs only if the coil is at 32 F / 0 C and the outdoor air is under 50 F / 10 C; otherwise only an abbreviated 30-second defrost happens. Quiet Shift-2 delays are included when that mode is on. The HK32EA003/008 defrost boards use a similar speed-up jumper (J1): short for 5 seconds then release; with the defrost thermostat open a short defrost of about 30 seconds results, with it closed a full cycle runs.
Applies to: Carrier single-stage communicating heat pump; HK32EA003/008 defrost boards
What to do
- Short the two-pin FORCED DEFROST header for 5 seconds, then release.
- On HK32EA003/008 boards, short the speed-up pins (J1) with a screwdriver for 5 seconds and release.
- On the Infinity single-stage communicating heat pump the same can be commanded from the user interface.
Other codes on the same units
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier residential A/C and heat pump service manual 24-25, Forced Defrost, p.48; HK32EA003/008 Defrost Control, p.17-18. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.