LC 06 Compressor top (IPM) temperature protection
What the control is telling you
Same protection as PC 02, shown by a different code on the chart. The IPM temperature is above the limit or the sampling voltage is not 5 V.
Applies to: Outdoor unit; shared chart with PC 02
Likely causes
- Blocked airflow at indoor or outdoor unit
- Refrigerant system fault
- Faulty or poorly connected OLP sensor
- Loose PCB or IPM radiator screws
Test and repair steps
- Clear the air inlet and outlet and clean the heat exchangers on the indoor and outdoor units.
- Turn the power off, wait 10 minutes and turn it back on.
- Check the compressor top temperature. If it is above 90 °C, check the refrigerant system and repair it if faulty.
- Check the OLP connection and correct it if loose.
- Measure the OLP resistance; replace the OLP if it is not zero.
- Check the PCB and IPM radiator screws are tight; tighten them and apply silicone grease.
- If the fault remains, replace the outdoor control PCB.
Models that show this code
7 models in D5CURA
Other codes on the same units
- 341 MCE error 341 MCE error
- EC 50 Temperature sensor open or shorted
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: D5CURA service manual, p. 41. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.