Carrier · Heat pump
EC 50 Temperature sensor open or shorted
What the control is telling you
Sampling voltage below 0.06V or above 4.94V. The display shows the failure code.
Applies to: D5CURA outdoor unit temperature sensor
Likely causes
- Sensor open or shorted
- Loose or faulty wiring to the PCB
- Sensor out of resistance range
- PCB fault
Test and repair steps
- Check the connection between the temperature sensor and the PCB and correct any wiring fault.
- Measure the sensor resistance and compare it with the appendix table (p. 88).
- If the resistance is out of range, replace the sensor.
- If the sensor is good, replace the outdoor PCB.
Models that show this code
7 models in D5CURA
Other codes on the same units
- 341 MCE error 341 MCE error
- LC 06 Compressor top (IPM) temperature protection
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Carrier D5CURA service manual, p. 35. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.