Viessmann · Mini-split · Cooling

Indoor fan running in COOLING mode

Vitocal IND-O

What happens, in order

  1. Indoor fan runs constantly in COOLING mode at high, medium, low or auto speed.
  2. When the setpoint is reached and the compressor stops, the indoor fan runs at the minimum speed or the selected speed.
  3. Fan speed follows the temperature difference bands (T1 minus Td) shown in Fig. 10.
  4. DIP switch SW2-1 sets whether the fan stops or runs at the lowest speed after the compressor stops.

Applies to: Indoor unit in cooling

Models

DLFSOAH09XAKDLFSOAH18XAK

More Viessmann mini-split sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: DLFSOAH Service Manual, p. 8. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.