Rinnai · Furnace · Startup

Normal start and heating

EX DT

What happens, in order

  1. Press ON/OFF on the control panel and the LED display lights, ON lamp is green
  2. Combustion fan starts (forced combustion)
  3. Spark ignites the main burner
  4. When flame is proven the ON lamp turns red and the spark stops
  5. Once the furnace warms up the room convection fan starts automatically
  6. Thermostat modulates the burner and the fan between L (minimum) and H (maximum) to hold the set temperature
  7. If power fails while running, the furnace restarts by itself when power returns

Timings and thresholds

ItemValue
Forced combustion before control logic takes overabout 15 to 18 s
Temperature setting range60 to 80 F in 2 F steps (or L / H)

Codes you may see during this

11

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct-vent room furnaces

Models

EX08DTEX11DTEX17DTEX22DT

More Rinnai furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai EX08DT and EX11DT Installation and Operation Manual (200000083) and EX17DT and EX22DT Installation and Operation Manual (200000084), operation and fault sections. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.