Rinnai · Furnace · Ignition

Ignition failure and flame loss retry

EX DT

What happens, in order

  1. If the burner does not light, the furnace waits and retries ignition after 1 hour
  2. Fault code 11 (ignition failure) shows during that hour and clears when ignition succeeds
  3. If the retry fails the code stays and another try follows in 1 hour
  4. If flame goes out during the forced combustion period the same 1 hour wait and code 11 apply
  5. If flame goes out after forced combustion, while the temperature control is running the burner, the furnace tries to relight immediately with no code
  6. This ignition-failure code is not saved in the fault history

Timings and thresholds

ItemValue
Retry delay after ignition failure1 h
Forced combustion periodabout 15 to 18 s

Codes you may see during this

11

Applies to: Rinnai EX08DT, EX11DT, EX17DT, EX22DT direct-vent room furnaces

Models

EX08DTEX11DTEX17DTEX22DT

More Rinnai furnace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai EX08DT and EX11DT Installation and Operation Manual (200000083) and EX17DT and EX22DT Installation and Operation Manual (200000084), operation and fault sections. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.