Rinnai · Tankless water heater · Pump/purge

Circ-Logic external recirculation pump

SENSEI RXRSCN-Series

What happens, in order

  1. Water heater PCB controls the on and off cycles of an external recirculation pump through its parameter settings
  2. Economy mode (05A) cycles the pump less often to save energy
  3. Comfort mode (05b) cycles the pump more often to keep the loop hotter
  4. Do not install a thermal bypass (crossover) valve on a dedicated return system

Codes you may see during this

63

Applies to: Rinnai tankless with external pump harness

Models

SENSEI RXRSCN-Series

More Rinnai tankless water heater sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Rinnai SENSEI RX Installation and Operation Manual (100000839), recirculation and parameter sections; also RSC and N-Series manuals, External Pump with Circ-Logic. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.