Majestic · Gas fireplace · Standby/shutdown

Signature Command: shutdown

DVBL7 Signature Command

What happens, in order

  1. OFF button pressed three times or held for 3 seconds (memory off), or wall switch turned off
  2. Main burner closes
  3. Standing pilot setups keep the pilot lit; intermittent setups shut the pilot as well
  4. Master switch OFF turns the whole system off
  5. Six-hour automatic shutdown stops the fireplace six hours after the last command (on by default)
  6. Wall switch to OFF turns burner off with memory off

Timings and thresholds

ItemValue
Auto shutdown6 hours after last command (default on)
Memory off hold3 s
Standing pilot temp offHold ON 3 s

Applies to: Signature Command models

More Majestic gas fireplace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Majestic DVBL7 Series Installation and Operating Instructions, p. 40, p. 47, p. 38. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.