Majestic · Gas fireplace · Heating

Signature Command: flame height control

DVBL7 Signature Command

What happens, in order

  1. ON pressed once burner at maximum flame
  2. OFF pressed once medium flame
  3. OFF pressed twice low flame
  4. OFF pressed three times main burner off
  5. Standing pilot setup pilot stays on
  6. Intermittent pilot setup pilot goes off too
  7. Smart / thermostat transmitters can modulate flame automatically

Applies to: Signature Command models

More Majestic gas fireplace sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Majestic DVBL7 Series Installation and Operating Instructions, p. 47, p. 39. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.