Kinghome · Heat pump · Defrost
Defrost and oil return
What happens, in order
- In heating, defrost starts when the outdoor coil sensor reaches the preset defrost temperature
- 4-way valve switches to the cooling position and the outdoor fan stops
- Defrost ends when the coil sensor reaches the preset stop temperature
- 4-way valve returns to heating, then compressor and outdoor fan restart
- Dip switch selects standard (default) or strong defrost; strong defrost runs longer for very cold conditions (switch 1 on the Eco outdoor board, switch 2 on the cold-climate board)
- Oil return after long low-frequency running the compressor is raised to an oil-return frequency for about 5 minutes
- Forced defrost (cold-climate board) hold SW1 about 5 s, short-press SW1 to function 06, press SW2 or SW3 to set ON, press SW1 to save; the menu exits after 10 s idle
Timings and thresholds
| Item | Value |
|---|---|
| Oil return duration | About 5 min |
| Menu idle timeout | 10 s |
| SW1 hold to enter debug | About 5 s |
Applies to: Kinghome Ultranixx ducted heat pump condensing units with air handlers
Models
More Kinghome heat pump sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Kinghome Ultranixx Eco KD24-60UHO outdoor + KD..UHI air handlers service manual, 2.1-2.3 Operation mode and control; Kinghome Ultranixx cold-climate ducted heat pump KU36UHO-KU60UHO service manual GC202306, 2.1-2.3. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.