Kinghome · Heat pump · Startup
Compressor, expansion valve and fan startup/stop rules
What happens, in order
- On a cooling or heating call the indoor fan runs for a while before the compressor starts
- On first power-up the electronic expansion valve resets (rattling sound is normal); before the compressor starts the valve opens to a set step
- After a start the compressor must run for a minimum time; after a stop it must rest several minutes before restart
- Outdoor fan speed is stepped from 1 (lowest) to 10 (highest) to allow low-ambient cooling and high-ambient heating; it does not run in fan mode
- In heating, the 4-way valve energizes a short while after heating starts; when heating stops it stays energized briefly then drops out
Applies to: Kinghome Ultranixx ducted heat pump condensing units with air handlers
Models
More Kinghome heat pump sequences
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Kinghome Ultranixx Eco KD24-60UHO outdoor + KD..UHI air handlers service manual, 2.1-2.3 Operation mode and control; Kinghome Ultranixx cold-climate ducted heat pump KU36UHO-KU60UHO service manual GC202306, 2.1-2.3. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.