Kinghome · Heat pump · Startup

Compressor, expansion valve and fan startup/stop rules

Ultranixx

What happens, in order

  1. On a cooling or heating call the indoor fan runs for a while before the compressor starts
  2. On first power-up the electronic expansion valve resets (rattling sound is normal); before the compressor starts the valve opens to a set step
  3. After a start the compressor must run for a minimum time; after a stop it must rest several minutes before restart
  4. Outdoor fan speed is stepped from 1 (lowest) to 10 (highest) to allow low-ambient cooling and high-ambient heating; it does not run in fan mode
  5. In heating, the 4-way valve energizes a short while after heating starts; when heating stops it stays energized briefly then drops out

Applies to: Kinghome Ultranixx ducted heat pump condensing units with air handlers

Models

KD24UHO-KD60UHOKU36UHO-KU60UHO

More Kinghome heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Kinghome Ultranixx Eco KD24-60UHO outdoor + KD..UHI air handlers service manual, 2.1-2.3 Operation mode and control; Kinghome Ultranixx cold-climate ducted heat pump KU36UHO-KU60UHO service manual GC202306, 2.1-2.3. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.