7 tips for heat pump: access codes, button combinations, test modes and the resets you need at the appliance.

Jump to: Access & passwords (1) · Service & test modes (5) · Settings shortcuts (1)

Access & passwords

Installer and service menu codes, and how to get into them.

Open the outdoor board debug menu (SW1 held 5 s)

Heat pump · Kinghome Ultranixx

Holding SW1 for about 5 seconds opens the first-level debug menu on the KU outdoor board; items include 06 forced defrost, 08 refrigerant recovery and 09 forced operation.

  1. Hold SW1 about 5 seconds until the board display flashes.
  2. Short-press SW1 to move to the item you need (06, 08 or 09).
  3. Use SW2 or SW3 to change the value, then short-press SW1 to save.
  4. Leave it alone for 10 seconds to exit.

Applies to: Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

Source: Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 2.3.5 to 2.3.7. Written in our own words; check the manual for your exact model.

Service & test modes

Forced fan, low and high fire, test and diagnostic modes, error history and live data.

Force a defrost cycle from the remote

Heat pump · Kinghome KM HEDI, Kinghome KM HT1DI

A key sequence on the remote forces the unit into defrost; the unit leaves it by itself when the outdoor unit finishes.

  1. Turn the unit on in heating mode and set 16°C.
  2. Within 5 seconds press + - + - + - on the remote.
  3. The unit exits the forced defrost by itself when the outdoor unit finishes.

Applies to: Kinghome KM09HEDI, KM12HEDI, KM18HEDI wall mini-splits; Kinghome KM09HT1DI, KM12HT1DI, KM18HT1DI, KM24HT1DI wall mini-splits

Source: Kinghome KM09-12-18HEDI service manual, sec. 7.8 compulsory defrosting function; Kinghome KM09-12-18-24HT1DI service manual, sec. 6.2 (8) compulsory defrosting function. Written in our own words; check the manual for your exact model.

Force a defrost from the outdoor board (debug item 06)

Heat pump · Kinghome Ultranixx

Item 06 turns forced defrost on (ON) or off (OF).

  1. Hold SW1 about 5 s, short-press SW1 until 06 shows.
  2. SW2 or SW3 chooses ON or OF.
  3. Short-press SW1 to save.

Applies to: Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

Source: Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 2.3.5 forced defrost control. Written in our own words; check the manual for your exact model.

Force cooling or heating from the outdoor board (debug item 09)

Heat pump · Kinghome Ultranixx

Item 09 forces the system to run regardless of the thermostat: 01 forced cooling, 02 forced heating, OF stops it.

  1. Hold SW1 about 5 s, short-press SW1 until 09 shows.
  2. SW2 or SW3 chooses 01 (cool), 02 (heat) or OF (off).
  3. Short-press SW1 to save.

Applies to: Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

Source: Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 2.3.7 forced operation control. Written in our own words; check the manual for your exact model.

Start refrigerant recovery from the outdoor board (debug item 08)

Heat pump · Kinghome Ultranixx

Item 08 switches refrigerant recovery (pump-down) on (ON) or off (OF).

  1. Hold SW1 about 5 s, short-press SW1 until 08 shows.
  2. SW2 or SW3 chooses ON or OF.
  3. Short-press SW1 to save.

Applies to: Kinghome Ultranixx cold-climate KU36UHO and KU60UHO outdoor units with KU..UH2I and KD..UHI air handlers

Source: Kinghome Ultranixx cold-climate KU36/60UHO service manual GC202306, sec. 2.3.6 refrigerant recovery control. Written in our own words; check the manual for your exact model.

Start the pilot (test) run from the remote

Heat pump · Kinghome KM HEDI

Runs the unit in cooling and shows dd on the indoor display while the pilot run is active.

  1. Cooling mode, set temperature 30°C.
  2. Within 3 seconds press + - + - + - on the remote.
  3. End the pilot run to clear dd.

Applies to: Kinghome KM09HEDI, KM12HEDI, KM18HEDI wall mini-splits

Source: Kinghome KM09-12-18HEDI service manual, sec. 7.10 pilot run function. Written in our own words; check the manual for your exact model.

Settings shortcuts

Where the useful parameters live and what they are set to from the factory.

Switch between defrosting mode 1 and 2

Heat pump · Kinghome KM HEDI

With the unit off, MODE and AUXILIARY together on the remote toggle the defrosting mode; H1 or H2 shows the mode the unit will use after it is switched on.

  1. With the unit off, press MODE and AUXILIARY together on the remote to switch between defrosting mode 1 and 2.
  2. H1 or H2 on the remote shows the mode selected.

Applies to: Kinghome KM09HEDI, KM12HEDI, KM18HEDI wall mini-splits

Source: Kinghome KM09-12-18HEDI service manual, sec. 7.7 switchover function for defrosting mode. Written in our own words; check the manual for your exact model.

Same tips in your pocket

The HVACopedia app has these tips, every error code and the settings tables offline.

Open the app

For licensed technicians. Installer menus, test modes and access codes change settings that affect safety; only use them if you are trained on the appliance and understand the result. Gas, electrical and refrigerant work must be done by a qualified, licensed person, and the manufacturer’s manual for the exact model and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.