Heat pump: time/temperature defrost and Quiet Shift 2

N4H4R4H4WCH4NXH5

What happens, in order

  1. Defrost interval is 30, 60, 90 or 120 min (quick connects on older boards, DIP switches on Quiet Shift 2 boards); on HK32EA011 and later aluminum-coil boards this is the first interval only and later intervals vary with defrost length
  2. Defrost thermostat closes at about 32 F; the timer runs only while the thermostat is closed and the contactor is energized
  3. In defrost the unit runs as in cooling except the outdoor fan is off and second-stage heat comes on
  4. Defrost ends when the thermostat opens at about 65 F, or after 10 minutes
  5. Quiet Shift 2 (DIP switch 3 ON, aluminum coil units): at start the compressor is off about 1 minute, then the reversing valve energizes, a few seconds later the compressor restarts and normal defrost runs; at the end the compressor is off about 1 minute again before the reversing valve de-energizes and the compressor returns to heating
  6. On HK32EA012 and later boards, Quiet Shift 2 turns off variable intervals so the DIP switch interval stays until the switch is changed and power cycled; a forced defrost resets the interval to the DIP setting
  7. Forced defrost on Quiet Shift 2 boards short the J1 speed-up pins for 5 s and release. With the thermostat open only a 30 s defrost occurs (Quiet Shift off) or a roughly 3 minute sequence (1 min compressor off, 30 s defrost, 1 min off) with it on
  8. Other boards close the defrost thermostat (cut power, disconnect outdoor fan from OF2/ODF, restart in heat until frost builds), short the speed-up pins (timing reduced to 1/25) and remove the short as soon as the reversing valve changes; the unit stays in defrost until the thermostat opens at about 65 F or the 10 minute timer ends

Timings and thresholds

ItemValue
Defrost interval30 / 60 / 90 / 120 min
Defrost startabout 32 F coil
Defrost endabout 65 F coil
Maximum defrost10 min
Quiet Shift 2 compressor-offabout 1 min at start and 1 min at end
Forced defrost pin hold5 s

Applies to: KeepRite / ICP N4H4, R4H4, WCH4, NXH5 heat pumps

Models

N4H4R4H4WCH4NXH5

More KeepRite heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP N4H4-R4H4-WCH4-NXH5 heat pump installation instructions 428 01 5107 10, Defrost and Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.