KeepRite · Heat pump · Defrost

Heat pump (Fast #1174185 board): defrost interval, Quiet Shift and speed-up test

Performance Series

What happens, in order

  1. Defrost thermostat closes at about 32 F and starts the DFT timing; interval choices are 30, 60, 90 and 120 min
  2. If the thermostat opens before the interval ends, timing resets
  3. At the end of the interval defrost starts; it ends when the thermostat opens at about 65 F or after 10 minutes
  4. Quiet Shift (DIP switch 3 ON, factory off): compressor is off 30 s going into defrost and 30 s coming out; fan stays off 40 s extra when returning to heating
  5. Forced defrost short the speed-up pins for 5 s and release. With the thermostat open a short 30 s defrost runs (Quiet Shift off) or about 1 minute (30 s compressor off, 30 s defrost) with Quiet Shift on
  6. Thermostat check with timer at 90 min the unit goes into defrost within about 21 s of shorting the speed-up pins; remove the screwdriver as soon as the reversing valve clicks or the control ends the cycle in about 2 s

Timings and thresholds

ItemValue
Defrost interval30 / 60 / 90 / 120 min
Defrost startabout 32 F coil
Defrost endabout 65 F coil
Maximum defrost10 min
Quiet Shift30 s compressor off in and out; fan off 40 s extra

Applies to: KeepRite / ICP / Tempstar / Heil Performance Series split heat pumps (defrost control Fast #1174185)

Models

Fast #1174185 control

More KeepRite heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP/Tempstar/Heil R-410A and R-22 split A/C and HP service manual 421 08 5400 04, System Function and Sequence of Operation, Defrost Control. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.