Heat pump: heating cycle with supplemental heat

N4H4R4H4WCH4NXH5

What happens, in order

  1. Thermostat makes R-Y and R-G on a call for heat
  2. R-Y energizes the contactor, starting outdoor fan and compressor; R-G starts the indoor blower on high speed
  3. If the room keeps falling, the second-stage thermostat makes R-W2, which energizes a relay for the first bank of supplemental electric heat and sends power on to the second heater relay if fitted
  4. If outdoor temperature falls below the field-installed outdoor thermostat setting, the second bank of supplemental heat comes on
  5. Thermostat satisfied contactor and relays drop out and heaters and motors stop

Applies to: KeepRite / ICP N4H4, R4H4, WCH4, NXH5 heat pumps

Models

N4H4R4H4WCH4NXH5

More KeepRite heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: KeepRite/ICP N4H4-R4H4-WCH4-NXH5 heat pump installation instructions 428 01 5107 10, Defrost and Sequence of Operation. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.