System test for inverter units
What happens, in order
- Run the system test on the inverter units before completing set-up.
- Complete the test with no errors to proceed through set-up.
- When the tests finish, the run test screen is shown.
- The test is complete only when display code E11 clears from the seven segment LED on the heat pump or air conditioner.
Codes you may see during this
Applies to: Inverter heat pump or air conditioner with Daikin One+
More Daikin furnace sequences
- Thermostat power-up and start-up screens · Startup
- Charge mode for refrigerant charging · Other
- Full set-up sequence · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 34. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.