Daikin · Furnace · Other
Charge mode for refrigerant charging
What happens, in order
- Select charge mode in System Optimization.
- The system runs steady for about 1 hour so refrigerant can be charged through the suction charge port.
- The system stops automatically when the run is complete.
- Follow the equipment installation manual for proper charging.
Timings and thresholds
| Item | Value |
|---|---|
| Steady operation in charge mode | approximately 1 hour |
Applies to: Inverter heat pump or air conditioner with Daikin One+
More Daikin furnace sequences
- Thermostat power-up and start-up screens · Startup
- Full set-up sequence · Other
- System test for inverter units · Other
Related
Take it to the job
Sequences of operation, error codes and tips work offline in the HVACopedia app.
Source: Daikin One+ Smart Thermostat Installation & Commissioning, p. 35. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.