Daikin · Water heater · Pump/purge

Release air and remove dust with the cascade pump

Mega-Q

What happens, in order

  1. On the remote controller, enter Field Settings and set mode 20, first code 8, second code 02 (setting 1, pump operation).
  2. Press On/Off to run the pump until air is gone.
  3. Press On/Off to stop the pump.
  4. Clean the strainer built into the cascade unit.
  5. Repeat the air release steps, because air enters when the strainer is cleaned.
  6. Close the upper and lower front panels.

Applies to: Cascade unit

More Daikin water heater sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Mega-Q installation manual, p. 42. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.