Airtight test and vacuum drying procedure

Mega-Q

What happens, in order

  1. Use tools dedicated to R410A and charge hoses with Schrader valve depressors.
  2. Connect nitrogen, refrigerant tank and vacuum pump to the heat source unit per the system diagram.
  3. Pressurize from the liquid or gas stop valve service port to 580 psi (4.0 MPa) with nitrogen.
  4. Hold for 24 hours and check for pressure drop.
  5. Fix any leak and repeat the airtight test if pressure drops.
  6. Evacuate from the liquid and gas stop valve service ports to 500 microns or less.
  7. Hold the system in vacuum for 1 hour and confirm the vacuum gauge does not rise.
  8. In rainy season, after 2 hours of evacuation, pressurize with nitrogen to 375,000 microns (vacuum break) and evacuate again for 1 hour to 500 microns or less.
  9. If 500 microns cannot be reached in 2 hours, repeat vacuum break and vacuum drying, then hold 1 hour and confirm the gauge stays flat.

Timings and thresholds

ItemValue
Airtight hold24 hours
Initial vacuum dryingmore than 2 hours
Vacuum hold check1 hour
Rainy-season re-evacuation1 hour

Applies to: Mega-Q refrigerant circuit

More Daikin water heater sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Daikin Mega-Q installation manual, p. 32. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.