Bosch · Heat pump · Defrost

Demand defrost

IDS LightPremium Connected2.0

What happens, in order

  1. Demand defrost control watches the outdoor coil (T3) against outdoor air (T4), run time and high pressure
  2. Any one condition starts defrost (1) coil-to-air temperature difference reaches the target for 3 minutes: air 39F or above needs 18F, 30F or above needs 16F, 19F or above needs 14F; below 19F air with coil under 9F needs 80 minutes of accumulated compressor run
  3. (2) minimum run time elapsed 4 hours when air is below 23F; 2 hours when air is 23F up to about 40F (42F on IDS 2.0)
  4. (3) high-pressure saturation temperature stays below 82F for 20 minutes (Light and Premium Connected limit this to air between 14F and 29F)
  5. Display shows dF with the compressor frequency while defrosting
  6. Defrost ends when the outdoor coil reaches 64F for 1 minute, or after 8 minutes
  7. SW5 options shorten heating time 10 percent, or extend defrost (120 s on Light, 60 s on Premium Connected and IDS 2.0)

Timings and thresholds

ItemValue
Delta T, air 39F or above18F
Delta T, air 30F or above16F
Delta T, air 19F or above14F
Delta T hold time3 min
Run time, air below 19F and coil below 9F80 min
Minimum run time, air below 23F4 h
Defrost endCoil 64F for 1 min, or 8 min max
Low-pressure defrost triggerBelow 82F saturation for 20 min

Codes you may see during this

dF

Applies to: Bosch IDS inverter heat pump condensing units

Models

BOVA15 (Light)BOVA36/48/60-20 (Premium Connected)BOVA-36-60HDN1 (IDS 2.0)

More Bosch heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Bosch IDS Light (BOVA15, R-454B) installation BTC 762003308 D, 17 System operation; Bosch IDS Premium Connected (BOVA36-60-20) installation BTC 762003301 D, 18 System operation; Bosch IDS 2.0 (BOVA-36-60HDN1) service manual Rev3 07.2021, 10.2 Other operations. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.