Bosch · Heat pump
dF Defrost in progress
What the display is showing
While the outdoor unit is defrosting, the board display shows dF with no digits after it. The unit leaves defrost on its own when the coil (T3) reaches 64 F for 1 minute or after 8 minutes. After a forced defrost test the display goes back to showing the running speed.
Applies to: BOVA IDS 2.0, IDS Premium Connected and IDS Light heat pumps
Models that show this code
7 models in Bosch IDS 2.0, Bosch IDS Light, Bosch IDS Premium Connected
Other codes on the same units
- Gateway cellular LED solid Gateway cellular LED (amber) steady - good signal
- Gateway fault LED off Gateway fault LED (red) off - no fault
- Gateway power LED 2 blinks Gateway power LED (green) 2 blinks - booting
- Gateway power LED solid Gateway power LED (green) steady - powered on
- PH Low discharge superheat protection
- Protection letter + Hz Limited operation - protection letter before the frequency
- Running readout Running - compressor frequency shown
- Standby readout Standby - outdoor ambient temperature shown
Sequence of operation
What the unit does around this code, step by step.
- Demand defrost · Defrost
- Manual (forced) defrost test · Defrost
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch IDS Premium Connected BTC 762003301 D (02.2025), 18.4 Defrost Description and 18.9 p.49; IDS Light BTC 762003308 D, 17.9 p.43; IDS 2.0 service Rev3 (07.2021), 10.2.1 Defrost Operation p.31. Summarized in our own words; check the original manual for your model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.