Bosch · Heat pump
PH Low discharge superheat protection
What the control is telling you
Discharge superheat is too low.
Applies to: Bosch IDS Light BOVA15-24/36/60 and IDS Premium Connected BOVA36-20/60-20 R-454B heat pump outdoor units
Likely causes
- Closed valves
- Undercharge
- Force mode left on
- Abnormal pressure
- T3/T5 sensor fault
Test and repair steps
- Open the service valves.
- Check the charge.
- Exit force mode.
- Check T3 and T5 resistance and replace if out of range.
Models that show this code
5 models in Bosch IDS Light, Bosch IDS Premium Connected
Other codes on the same units
- Gateway cellular LED solid Gateway cellular LED (amber) steady - good signal
- Gateway fault LED off Gateway fault LED (red) off - no fault
- Gateway power LED 2 blinks Gateway power LED (green) 2 blinks - booting
- Gateway power LED solid Gateway power LED (green) steady - powered on
- Protection letter + Hz Limited operation - protection letter before the frequency
- Running readout Running - compressor frequency shown
- Standby readout Standby - outdoor ambient temperature shown
- dF Defrost in progress
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Bosch IDS Light installation BTC 762003308 D (02.2025), Fault Code Table 23 and 17.12 Error Code Troubleshooting, p.42-59; Bosch IDS Premium Connected installation BTC 762003301 D (02.2025), Fault Code Table 22 and 18.12 Error Code Troubleshooting. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.