Bosch · Heat pump · Other

Oil return and force (charge) mode

IDS 2.0

What happens, in order

  1. Oil return runs when the compressor has been at low speed for a long time; the display shows A with the compressor frequency
  2. Force mode is entered manually from the Force button and forces the compressor to 100 percent capacity in cooling, used for checking superheat/subcooling and charging
  3. Display shows a dash pattern with the frequency during force mode

Applies to: Bosch IDS 2.0 heat pump condensing units

Models

BOVA-36-60HDN1

More Bosch heat pump sequences

Take it to the job

Sequences of operation, error codes and tips work offline in the HVACopedia app.

Open the app

Source: Bosch IDS 2.0 (BOVA-36-60HDN1) service manual Rev3 07.2021, 10.2 Other operations. Written in our own words; timings can differ by model and software version, so check the manual for your exact unit.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.