Works, then warms up (repeating)

What is going on

The old story on a unit that cools, then warms up, then cools again is moisture. Water in the refrigerant freezes at the metering device, plugs it, then the ice melts when the unit warms and the cycle starts over. I've seen it a hundred times after a sloppy repair. It has to be fixed properly, not just by adding refrigerant.

Likely causes

  • Moisture in the refrigerant freezing at the metering device and blocking flow
  • A saturated or missing drier that no longer holds the water

Check in this order

  1. Confirm by gently warming the metering device during the off cycle and watching whether flow returns
  2. Recover and filter the charge using proper recovery equipment (licensed tech)
  3. Install a new liquid-line drier
  4. Evacuate to a deep vacuum
  5. Recharge to the correct weight
  6. Run the unit and watch for a repeat of the warm-up cycle

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.