Coldest evaporator warms on off cycle / poor refrigeration in coldest case

What is going on

On a multi-case rack, the coldest case is the one that suffers most when the compressors cycle off. If it warms up on the off cycle, warm vapor from the cases running at a higher EPR setting can sneak back into the coldest case and condense there. That is what a check valve at the coldest coil outlet is for, so start by finding out whether it is missing, leaking or too small.

Likely causes

  • Check valve at the coldest evaporator outlet is missing or leaking, so warm vapor from the EPR coils migrates in and condenses
  • Check valve undersized or sticking, so it throttles flow and costs capacity

Check in this order

  1. Find the check valve at the coldest coil outlet and confirm it is installed in the right flow direction
  2. Measure the pressure drop across it while running, because a large drop means undersized or sticking
  3. Check for warming on the off cycle by watching case temperature and suction line temperature after shutdown
  4. Replace a leaking or sticking valve with one sized for the coil

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.