Compressor short cycles on LPC after shutdown
What is going on
What I usually find on a compressor that short cycles right after it shuts down on low pressure is a liquid line solenoid that doesn't seal. The suction side slowly fills back up, the pressure climbs past the cut-in, and the compressor starts again for a few seconds. That is hard on the compressor and the starting components, so don't leave it.
Likely causes
- Liquid line solenoid leaking through its seat
- TXV leaking, letting refrigerant feed the evaporator after shutdown
- Low-pressure control cut-in set too low or cut-out set too high, so the differential is too tight
- Non-recycling relay missing, so the pump-down is not latched out
Check in this order
- Put gauges on and watch suction pressure after cut-out. It should hold, with about a 2 psi cut-out typical, instead of climbing quickly.
- If pressure rises fast, check the solenoid seat and the TXV for leak-through
- Verify the low-pressure control settings against the manual for the system
- Look at the relay wiring to see that a non-recycling relay is installed and wired correctly
- Retest a full pump-down and count the starts over an hour
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.