Won't cut in / won't cut out
What is going on
When a refrigeration control won't cut in or won't cut out, nine times out of ten it's the thermostat itself, either drifted out of calibration or with burnt points. I've seen plenty of these chatter or hang closed. A bath test will tell you quickly whether the control is telling the truth.
Likely causes
- Faulty thermostat with pitted or stuck contacts
- Calibration drift so the cut-in and cut-out points are off from the setting
Check in this order
- Pull the control's sensing bulb or probe and check it is seated and reading the right spot
- With power off, check the contacts for continuity as you move the setpoint, the way the manufacturer's test shows
- Put the sensing element in an ice-water bath and watch whether the contacts open and close at the expected point
- Use a data logger if the problem comes and goes
- Check the control against the cut-in and cut-out settings for that unit
- Replace the control if the contacts don't open and close cleanly or if it chatters. Never leave a control bypassed
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.