Water overflow / drain pan full / condensate pump alarm

What is going on

Water over the pan edge or a pump alarm. Drain's backed up or the pump isn't moving water. Check drain path first, then pump.

Likely causes

  • Plugged drain from slime or debris
  • Pump float stuck
  • Pump vent covered
  • Outlet check valve failed, so water falls back into the pan
  • Algae buildup in the pan and lines

Check in this order

  1. Cut power to the pump and coil before reaching in.
  2. Clear the drain with a wet vac or flush. Don't push debris deeper.
  3. Lift the pump float by hand and see if the pump starts and the alarm clears.
  4. Make sure the pump vent isn't taped, capped or blocked.
  5. Pump water out and see if it flows back. Backflow means a bad check valve, replace it.
  6. Scrub the pan and flush the lines, then treat with a pan tablet or cleaner to keep algae down.

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.