Valve won't open on warm start / long pull-down

What is going on

If a valve won't open on a warm start and the pull-down drags on, don't assume it is bad. A gas-charged or pressure-limited valve with a MOP feature holds itself closed until the suction pressure drops below the MOP, and that is normal. Only after that do I suspect a lost bulb charge.

Likely causes

  • MOP (gas-charged or pressure-limited) valve holding closed until suction pressure falls below the MOP, which is normal
  • Lost bulb charge

Check in this order

  1. Compare suction pressure with the valve's MOP rating
  2. Warm the bulb in your hand and watch for a response
  3. If the valve never responds, the bulb has probably lost its charge and the valve needs replacing
  4. Recover refrigerant before changing it, licensed technician only

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.