Vacuum won't reach target or rises steadily after isolating

What is going on

The vacuum will not come down to target, or it climbs steadily once you close the valve and isolate the pump. A leak is the usual reason.

Likely causes

  • Leak in the system, hoses or connections that lets air in
  • The leak is the problem, so more pumping time will not fix it

Check in this order

  1. Isolate the pump with the gauge valve and watch the micron gauge for a steady rise, because a leak climbs without leveling off
  2. Repair leaks first, because a leaking system can never be dehydrated no matter how long you pump
  3. Tighten hose fittings and check core tools and gaskets
  4. Re-pull the vacuum after the repair and confirm it holds
  5. If you cannot find the leak, pressure test with nitrogen and bubbles before evacuating again

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.