Vacuum rises then levels off above 500 microns

What is going on

What I usually find when the vacuum rises and then levels off above 500 microns is moisture, not a leak. Water boils off slowly under vacuum and the gauge climbs until it reaches the water vapor pressure for that temperature, then it sits there. A leak keeps climbing, a wet system plateaus. If the plateau sits near 5000 microns you are probably looking at ice or liquid water still in the system.

Likely causes

  • Moisture in the system, with the plateau sitting at the water vapor pressure for that temperature
  • A plateau around 5000 microns means ice or liquid water is still present

Check in this order

  1. Warm the system evenly with heat lamps or room heat and keep pumping, since cold water will not boil off
  2. Look for a frost or sweat spot, which shows where the water is hiding
  3. Isolate and watch whether the rise levels off or keeps climbing, to tell moisture from a leak
  4. Break the vacuum with dry nitrogen and replace the drier if it is saturated
  5. Pull the vacuum down again and confirm it holds below 500 microns

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.