Unit will not run
What is going on
Most of the time a refrigerator or freezer that won't run at all comes down to something simple like a blown fuse, low voltage at the outlet or a cord problem. After that I go through the start components and the control, then the compressor last. Start with the outlet and work your way in, since it's the cheapest thing to check. Unplug the unit before touching any wiring.
Likely causes
- Blown fuse, low voltage, or a bad power cord
- Bad temperature control, relay or overload
- Broken lead to the compressor, timer or thermostat
- Bad defrost timer
- Bad compressor
Check in this order
- Replace the fuse and check the outlet, which should read 115 V within 10 percent
- Low voltage reduce the load on the circuit or give the unit its own circuit. An auto-transformer is a last resort.
- Test the temperature control for continuity across its terminals with the unit unplugged, and replace it if it is open when it should be closed. Never leave a control bypassed.
- Test or replace the relay and overload
- Put a test light at the outlet and then at the unit to find a bad cord
- Repair broken leads and test the defrost timer with a test light
- Use a manual test cord on the compressor last
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.