Uneven coil temperatures, part of coil warm

What is going on

Coil warm in spots, cold in others. Feed is uneven. Some circuits starved. Cold ones get the refrigerant, warm ones get little or none. You lose capacity and sometimes frost only part of the coil.

Likely causes

  • Distributor tube plugged
  • Distributor undersized or wrong nozzle
  • Uneven feed across circuits
  • Restriction ahead of the distributor, such as a blocked strainer

Check in this order

  1. Measure the temperature of each circuit with a thermometer. A circuit well off from the rest is starved.
  2. Check superheat at the suction outlet to see how the whole coil is doing.
  3. Inspect the distributor tubes for blockage or kinks.
  4. Compare the distributor and nozzle to the coil's specification.
  5. Check the liquid line and strainer for a restriction upstream.
  6. Recover refrigerant before removing parts, licensed technician only.
  7. Recheck circuit temperatures after the repair.

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.