Tube pitting or scaling

What is going on

Pitting or scale in water-cooled condenser or chiller tubes tells you something about the water speed through them. Flow that is too fast eats the tube wall, and flow that is too slow lets scale settle. It's worth catching early, because tube replacement is expensive.

Likely causes

  • Water velocity over 10 fps, which causes pitting and erosion
  • Water velocity under 7 fps, which allows scale to deposit

Check in this order

  1. Measure the water flow and work out the velocity through the tubes
  2. Correct the flow to stay between 7 and 10 fps
  3. Inspect the tubes after the correction
  4. Descale or clean tubes as needed
  5. Check water treatment too

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.