Thermal overload trips repeatedly

What is going on

A compressor that keeps kicking off on its thermal overload usually has a reason, and resetting it is not a fix. What I usually find is a dirty condenser or poor air around the compressor driving the head up, so check that before blaming the compressor. After that it comes down to oil, windings and liquid coming back. Let it cool and find the cause.

Likely causes

  • High ambient or poor airflow around the compressor
  • Dirty or blocked condenser giving high head pressure
  • Low oil
  • Shorted windings
  • High suction pressure during a hot pull-down
  • Liquid floodback

Check in this order

  1. Turn the power off and check airflow around the compressor
  2. Check condenser cleanliness and head pressure
  3. Measure amps and compare with RLA
  4. Check the oil level
  5. Measure winding resistance and megohm to ground
  6. Check suction pressure on start-up
  7. Do not bypass or keep resetting the overload

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.