System pressures don't match P/T chart / high head with normal load
What is going on
Gauge readings that do not line up with the P/T chart, or head pressure that is high on a normal load.
Likely causes
- Air or other non-condensables in the system, because they add to head pressure without adding cooling
- This usually follows a poor evacuation or a service job that let air in
Check in this order
- Compare saturation temperature with the actual condenser temperature to confirm the pressure is too high for the refrigerant
- Check condenser cleanliness and fan operation first so you rule out the common causes
- Recover the refrigerant with a recovery machine, never vent it
- Evacuate properly to a deep vacuum and confirm it holds
- Recharge by weight and recheck pressures against the chart
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.