Suction pressure/temperature drops too low, system cycles off early, coil freezes
What is going on
Suction drops too low, unit short cycles off on low pressure, coil freezes. Typical low-load problem. Bypass isn't giving the compressor enough load, or discharge temp is running high from the other side.
Likely causes
- Hot-gas bypass valve not opening, or set too low
- Temperature-type bypass controller or sensor fault
- Liquid injection valve not desuperheating, so discharge runs too hot
Check in this order
- Compare the bypass valve setting with actual suction pressure at low load. Suction under setting means the valve is not opening.
- Check the controller and sensor on a temperature-type bypass for correct readings
- Take discharge temperature at the compressor, high discharge points at the injection side
- Check the injection valve bulb placement and read superheat
- Call a licensed refrigeration tech for valve replacement or resetting
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.