Suction line heavily frosted at start-up, compressor struggles to start, possible slugging
What is going on
Heavy frost on the suction line at start-up with the compressor struggling to turn over means liquid is reaching it. Possible slugging. It is worst on systems with no receiver, where excess refrigerant has nowhere to sit but the evaporator and compressor.
Likely causes
- Overcharge on a system with no receiver, since liquid has nowhere to sit
- Evaporator filling with liquid during the off cycle, then flooding the compressor at start
- Crankcase heater not working, so refrigerant migrates to the oil
- Metering device leaking through on the off cycle
Check in this order
- Charge by weight to the nameplate, because slugging happens when charge is guessed.
- Check the crankcase heater has been on long enough, since cold oil soaks up refrigerant.
- Verify there is no liquid at the compressor by feeling and watching the suction line frost pattern.
- Check superheat at the compressor inlet. Low or near zero superheat means liquid is returning.
- Recover the excess properly, licensed technician only.
- Watch the suction line at the next start for frost.
- Listen at start for knocking and shut down if it persists.
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.