Starved evaporator / low capacity

What is going on

Evaporator starved, capacity down. Low suction pressure and warm product are what you see. The valve is not passing enough refrigerant for the load, either because of how it is set or sized.

Likely causes

  • Undersized valve
  • Setting too low
  • High altitude not compensated for
  • Plugged inlet screen

Check in this order

  1. Adjust in the CW direction to raise the low-side pressure, in small steps, waiting between each.
  2. Compensate for altitude, since thin air changes the settings.
  3. Clean the inlet screen, because a plugged one limits flow.
  4. Check valve sizing against the load.
  5. Measure superheat before and after so you know the change helped.
  6. Check for a restriction in the liquid line or drier.
  7. Recover refrigerant before opening the valve, licensed technician only.

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.