Sight glass shows bubbles

What is going on

Bubbles in the sight glass make a lot of people reach for the refrigerant cylinder, and that is a mistake. On cap-tube systems some flash in the liquid line is normal and does not mean low charge. I have seen plenty of units overcharged because someone chased bubbles. Check it properly before adding anything.

Likely causes

  • Not necessarily low charge, since liquid-line flash is normal on cap-tube systems
  • Pressure drop in the liquid line or a warm condenser can also show bubbles

Check in this order

  1. Do not add refrigerant just because the glass shows bubbles
  2. Check the charge by weight if you know the nameplate amount
  3. Check superheat for a fixed-restrictor system
  4. Compare pressures against the manufacturer's chart
  5. Check the filter-drier and liquid line for a temperature drop that points to a restriction

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.