Repeat compressor burnout

What is going on

Compressor keeps burning out. Replacing it again without fixing the reason is a waste. Something is killing it: contamination, heat, voltage or lack of cooling.

Likely causes

  • Moisture or dirt left in the system from the last job
  • High head pressure from a dirty condenser
  • Low supply voltage
  • Bad safety devices that let it run when it shouldn't
  • Low charge, so the motor doesn't get cooled by returning vapour

Check in this order

  1. Acid test the oil before anything else
  2. Flush the system
  3. Install new drier(s), including a suction drier
  4. Clean the condenser
  5. Measure head pressure after the repair and confirm it is normal
  6. Replace the bad controls and check line voltage under load

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.