Refrigerant/oil leak at shaft
What is going on
Refrigerant or oil weeping at the compressor shaft on a belt-driven compressor.
Likely causes
- Worn shaft seal from belt over-tension, because it loads the shaft sideways
- Pulley misalignment
- Shafts not parallel
- Lack of lubrication at the seal faces
Check in this order
- Power off and lock out before reaching near the belt and pulley
- Check belt tension and pulley alignment
- Check that the shafts are parallel
- Inspect the seal faces
- Replace the seal; recover refrigerant first, licensed technician only
- Fix the cause before restarting or the new seal will fail too
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.