Refrigerant migration / flooded compressor after power failure

What is going on

After a power failure the compressor can come back on with liquid refrigerant sitting in the crankcase or the suction side, and that is how compressors get slugged. Before restarting anything, confirm the unit was down long enough for refrigerant to migrate to the coldest part of the system, which is usually the compressor. This one is mostly a design issue on systems with a stepper electronic expansion valve, so a repeat problem needs a licensed refrigeration technician to look at the piping and controls.

Likely causes

  • A stepper EEV holds its last position with no power, so it can stay open and let liquid run through to the evaporator and on to the compressor during the outage
  • No positive shutoff in the liquid line, so refrigerant keeps moving to the cold side while the unit is off
  • Crankcase heater not energized or not working, which lets refrigerant dissolve into the oil

Check in this order

  1. Disconnect power and lock out before opening any panels, then do not bump the compressor on to see if it runs
  2. Check whether the crankcase heater has been energized long enough to boil off refrigerant from the oil, and verify it draws current with a clamp meter
  3. Feel the compressor shell and suction line for cold or sweating, which points to liquid present
  4. Look at the EEV controller to see what position it reports after power returns
  5. Add a liquid line solenoid valve that closes when power is lost, wired so it cannot stay open without control power
  6. Recheck that the new solenoid closes on a simulated power drop before returning the unit to service

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.