Refrigerant loss with no visible leak

What is going on

When a system keeps losing refrigerant and you cannot find a leak with a bubble test or a detector, the leak is often a safety device that opens when it should not. Relief valves, fusible plugs and rupture discs all vent refrigerant, and sometimes the escape is small enough that you do not notice it. Do not just top off the charge, because the cause will be back and refrigerant is regulated.

Likely causes

  • Relief valve weeping from debris on the seat after a discharge, corrosion, or a broken seal
  • Fusible plug failed from age or heat
  • Rupture disc burst, which the gauge will show as pressure
  • Stacked relief valves changing the effective setting

Check in this order

  1. Inspect the relief valve outlet for oil, frost or staining
  2. Purge the relief line of water and debris so it cannot corrode the seat
  3. Look at the rupture disc gauge for pressure between the disc and the relief valve
  4. Replace any relief valve after it has discharged
  5. Replace relief valves at the 5-year interval
  6. Have a licensed technician recover, repair and recharge

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.