Product partially thawed / ice crystals on product; box warms during defrost

What is going on

When product starts to thaw and gets ice crystals on it, I look at the defrost cycle before anything else. Nine times out of ten the coil is getting cooked too long, and all that extra heat dumps into the box. Fans running during defrost make it worse because they blow warm, wet air right onto the product.

Likely causes

  • Over-defrosting: time termination set too long, or the termination thermostat set too high or failed
  • Evaporator fan running during defrost and pushing heat into the box
  • Termination stat not sensing the coil properly, so defrost keeps going after the coil is clear

Check in this order

  1. Set up defrost to end on temperature or pressure, with time as a backup only
  2. Set the termination setpoint around 40°F at the coil, and confirm it with a thermometer on the coil
  3. Check that the fan delay is working so the fans stay off until the coil drains and refreezes the leftover water
  4. Test the termination thermostat and replace it if it does not open at its setting
  5. Shorten the time backup once termination is working, then watch box temperature through a full defrost
  6. Take a product temperature reading before and after to confirm the fix

More refrigeration guides

Take it to the job

All guides, error codes and tips work offline in the HVACopedia app.

Open the app

Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.