Pressure/temperature control faults (refrigerators, coolers, freezers)
What is going on
On refrigerators, coolers and freezers, nine times out of ten the pressure or temperature control is the culprit when the box runs wrong, and the usual finding is worn contacts. Next is a control that has lost its charge, or a sensing bulb that was never clamped right. Check them in that order and you save yourself a lot of guessing.
Likely causes
- Corroded or pitted contacts
- Overload on the contacts
- Lost bellows or diaphragm charge
- Sensing element not tight on the evaporator, or mounted in the wrong place
Check in this order
- Power off first, then ohm across the contacts for resistance; replace the control, since filing is only temporary
- Press the bellows; a charged one will not compress by finger, and one that squashes easily has lost its charge, so replace the element or control
- Re-clamp the bulb on the last third of the evaporator with cleaned surfaces
- Confirm the setting and differential against the manufacturer's data
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.