Pressure drops over 1 h / 24 h
What is going on
When the pressure drops over an hour or a day on a standing test, I've almost always found a leak. Temperature swings can fool you a bit, so note the ambient when you start. But a steady drop is a leak until proven otherwise. Start with the obvious places, joints, flares and tubing that rubs against something.
Likely causes
- A leak, at a joint, flare, fitting or where tubing rubs against a bracket or panel
- A small leak hiding in a coil or a place that is hard to reach
Check in this order
- Bubble-test every joint, flare and rubbing spot with solution
- If you find nothing, add a trace charge of about 10% refrigerant, topped up with nitrogen
- Sweep the system with an electronic detector
- Repair the leak and re-pressure test
- Hold the test long enough to confirm the pressure stays put
More refrigeration guides
Take it to the job
All guides, error codes and tips work offline in the HVACopedia app.
Source: General HVAC service practice — verify per model. Written in our own words; check the manual for your exact model.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.